The SIRCO MOT AT is a motorised load break switch incorporating a multipolar power section and motorised control unit. The manual covers 3- and 4-pole configurations, auxiliary power supply, position indication, Auto/Manual selection, emergency manual operation, padlocking, and input/output contacts.

Socomec

Installation Manual

English

Socomec

Installation Manual

English

Manual Overview
This page hosts the Socomec SIRCO MOT AT Manual, covering product identification, environmental conditions, installation, connections, operating modes, electrical operation, manual operation, accessories, and troubleshooting. The manual provides technical information for installation, commissioning, operation, and maintenance of Socomec SIRCO MOT AT motorised switches.

Technical Specs

Parameter Value
Document Reference 543339D
Current Range 125A to 3200A
Frame Sizes B3-B5 (125-630A), B6-B7 (800-1600A), B8 (3200A)
Poles 3 or 4 poles (multipolar load break switch)
Auxiliary Power Supply (AC) 230 VAC (208-277 VAC ±20%)
Auxiliary Power Supply (DC) 12 VDC or 24 VDC (for 125-1600A range)
IP Rating (Control Unit) IP2X against direct contact
IP Rating (Power Section, with shields) IP2X against direct contact
IP Rating (Power Section, no shields) IP0
Operating Temperature (no derating) -20°C to +40°C
Operating Temperature (with derating) -20°C to +70°C (Kt factor applies)
Mechanical Endurance (Aux. Contacts) 8000 cycles
Response Time 5-10 ms
Startup Duration 200 ms

Control Terminal Reference

Terminal / Contact Function
301 – 302 Auxiliary power supply input (208-277 VAC ±20%)
313 & 317 Override control / force switch to Off position — must be open for normal electrical operation
312 – 317 Order inputs — caution: must never be connected to any power supply
63A / 64A Product availability output contacts — closed indicates product available
Output Contacts (x3)  Position indication (I-O) and product availability outputs
Input Contacts (x4) Position order I-O, remote control enable, override/force-to-off controls

Troubleshooting Guide

Symptom Checks
Switch does not operate electrically Verify power supply on terminals 301-302 (208-277 VAC ±20%); confirm front selector is in AUT position; confirm contacts 313 and 317 are open; confirm green power LED is on and red fault LED is off; confirm contacts 63A/64A are closed (product available)
Cannot operate switch manually Confirm front selector is in Manual position; confirm the unit is not padlocked; verify handle rotation direction; apply sufficient progressive force in the indicated direction
Electrical operation doesn’t match external order I/O Verify the selected control logic wiring (impulse or contactor); check connector connections
Fault/Manual LED is on Normal in Manual mode; in AUT mode, indicates an internal fault — cycle AUT to Manu and back to AUT to reset; also normal when contact 313 is closed with 317 (forced to Off); if it remains on abnormally, contact Socomec
Impossible to padlock Confirm front selector is in manual position; confirm emergency handle is not inserted; confirm unit is in 0 position (padlocking only possible in 0 position on standard products)

Related Manuals

Socomec ATyS M Series 40-160A ATS Manual

The ATyS M range includes several control variants suited to different applications.

Baudouin TJ275BD5L DSE7320 Control Panel Drawing

Control panel design for a generator set built around the Baudouin 6M16G275/5 engine and a DSE7320 MKII controller.

ASCO 962 ATS Bypass-Isolation Switches Operator’s Manual

This manual provides information and control of the ATS's operation.

Important Safety Notice: Before installing, operating, servicing, or troubleshooting this equipment, verify that this manual matches your exact model and serial number. Always read and follow the manufacturer's safety instructions.

Read Online

Loading manual…

More From

ATS Panel

Socomec ATyS M Series 40-160A ATS Manual

Socomec ATyS M Series 40-160A ATS Manual

The ATyS M range includes several control variants suited to different applications.

Baudouin TJ275BD5L DSE7320 Control Panel Drawing cover

Baudouin TJ275BD5L DSE7320 Control Panel Drawing

Control panel design for a generator set built around the Baudouin 6M16G275/5 engine and a DSE7320 MKII controller.

ASCO 962 ATS Bypass-Isolation Switches Operator's Manual cover

ASCO 962 ATS Bypass-Isolation Switches Operator’s Manual

This manual provides information and control of the ATS's operation.

Free, and staying that way

Saved hundreds on a technician call? A quick $3 coffee keeps this independent library running and growing.

☕ Buy the Archivist a Coffee

Spot something off?

Wrong revision, dead link, or spec that doesn't match your unit? Tell us, and we'll check it.

Report an Issue